Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 129

Advertising
background image

Technical data of CPU 31xC

6.4 CPU 313C-2 PtP and CPU 313C-2 DP

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

6-19

Technical data

CPU 313C-2 PtP

CPU 313C-2 DP

DP slave

Number of connections

8

Services

PG/OP communication

Yes

Routing

Yes (only if interface is active)

Global data communication

No

S7 basic communication

No

S7 communication

No

Direct data exchange

Yes

Transmission rates

Up to 12 Mbps

Automatic baud rate search

Yes (only if interface is passive)

Intermediate memory

244 bytes I / 244 bytes O

Address areas

Max. 32, with max. 32 bytes each

DPV1

No

GSD file

The latest GSD file is available at:
http://www.ad.siemens.de/support
in the Product Support area

Point-to-point communication

Transmission rates

38.4 kbps half duplex

19.2 kbps full duplex

Cable length

Max. 1200 m

User program can control the interface Yes

The interface can trigger a break or an

interrupt in the user program

Yes (message with break ID)

Protocol driver

3964(R); ASCII

Programming

CPU 313C-2 PtP

CPU 313C-2 DP

Programming language

LAD/FBD/STL

Available instructions

see the Instruction List

Nesting levels

8

System functions (SFCs)

see the Instruction List

System function blocks (SFBs)

see the Instruction List

User program security

Yes

Integrated I/O

CPU 313C-2 PtP

CPU 313C-2 DP

Default addresses of the integrated

Digital inputs

Digital outputs


124.0 to 125.7
124.0 to 125.7

Advertising