A.1.2 changed behavior of certain sfcs – Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 208

Advertising
background image

Appendix

A.1 Information about upgrading to a CPU 31xC or CPU 31x

CPU 31xC and CPU 31x, Technical data

A-2

Manual, Edition 08/2004, A5E00105475-05

... then please note if you upgrade to one of the following CPUs

From version

CPU

Order number

Firmware

Hardware

Hereafter called

312

6ES7312-1AD10-0AB0

V2.0.0

01

312C

6ES7312-5BD01-0AB0

V2.0.0

01

313C

6ES7313-5BE01-0AB0

V2.0.0

01

313C-2 PtP

6ES7313-6BE01-0AB0

V2.0.0

01

313C-2 DP

6ES7313-6CE01-0AB0

V2.0.0

01

314

6ES7314-1AF10-0AB0

V2.0.0

01

314C-2 PtP

6ES7314-6BF01-0AB0

V2.0.0

01

314C-2 DP

6ES7314-6CF01-0AB0

V2.0.0

01

315-2 DP

6ES7315-2AG10-0AB0

V2.0.0

01

315-2 PN/DP

6ES7315-2EG10-0AB0

V2.3.0

01

317-2 DP

6ES7317-2AJ10-0AB0

V2.1.0

01

317-2 PN/DP

6ES7317-2EJ10-0AB0

V2.3.0

01

CPU 31xC/31x

Reference

If you intend to migrate from PROFIBUS DP to PROFINET, we also recommend the

following manual:

Guide: From PROFIBUS DP to PROFINET IO

See also

DPV1 (Page 3-32)

A.1.2

Changed behavior of certain SFCs

SFC 56, SFC 57 and SFC 13 which work asynchronously

Some of the SFCs that work asynchronously, when used on CPUs 312IFM – 318-2 DP, were

always, or under certain conditions, processed after the first call ("quasi-synchronous").
On the 31xC/31x CPUs these SFCs actually run asynchronously. Asynchronous processing

may cover multiple OB1 cycles. As a result, a wait loop may turn into an endless loop within

an OB.
The following SFCs are affected:

SFC 56 "WR_DPARM"; SFC 57 "PARM_MOD"
On CPUs 312 IFM to 318-2 DP, these SFCs always work "quasi-synchronously" during

communication with centralized I/O modules and always work synchronously during

communication with distributed I/O modules.