6 global data communication (mpi only) – Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 37

Advertising
background image

Communication

3.2 Communication services

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

3-9

3.2.6

Global data communication (MPI only)

Properties

Global data communication is used for cyclic exchange of global data via MPI subnets (for

example, I, Q, M) between SIMATIC S7 CPUs (data exchange without acknowledgement).

One CPU broadcasts its data to all other DP CPUs on the MPI subnet. This function is

integrated in the CPU operating system.

Reduction ratio

The reduction ratio specifies the cyclic intervals for GD communication. You can set the

reduction ratio when you configure global data communication in STEP 7. For example, if

you set a reduction ratio of 7, global data are transferred only with every 7th cycle. This

reduces CPU load.

Send and receive conditions

Conditions which should be satisfied for GD communication:

For the transmitter of a GD packet:

Reduction ratio

transmitter

x cycle time

transmitter

≥ 60 ms

For the receiver of a GD packet:

Reduction ratio

receiver

x cycle time

receiver

< reduction ratio

transmitter

x cycle time

transmitter

A GD packet may be lost if you do not adhere to these conditions. The reasons being:

the performance of the "smallest" CPU in the GD circuit

asynchronous transmitting / receiving of global data at the stations

When setting in STEP 7: “Transmit after each CPU cycle“, and the CPU has a short scan

cycle time (< 60 ms), the operating system might overwrite a GD packet of the CPU before it

is transmitted. The loss of global data is indicated in the status box of a GD circuit, if you set

this function in your STEP 7 configuration.

Advertising