Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 164

Advertising
background image

Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data

6-54

Manual, Edition 08/2004, A5E00105475-05

Technical data
Permitted potential difference

between M

ANA

and M

internal

(U

ISO

)

75 VDC / 60 VAC

Insulation test voltage

600 VDC

Analog value generation
Resolution (including overdrive)

11 bits + signed bit

Conversion time (per channel)

1 ms

Settling time

with resistive load

0,6 ms

With capacitive load

1,0 ms

With inductive load

0.5 ms

Interference suppression, error limits
Crosstalk between the outputs

> 60 dB

Operational error limits (across the temperature range, in relation to output

range)

Voltage/current

± 1 %

Basic error limit (operational limit at 25 °C, in relation to output range)

Voltage/current

± 0,7 %

Temperature error (in relation to output range)

± 0.01 %/K

Linearity error (in relation to output range)

± 0,15 %

Repeat accuracy (in transient state at 25 °C, in relation to output range)

± 0,06 %

Output ripple; bandwidth 0 to 50 kHz (in relation to output range)

± 0,1 %

Status, interrupts, diagnostics
Interrupts

no interrupts when operated as standard

I/O

For using technological functions, please

refer to the

Technological Functions

Manual.

Diagnostics functions

no diagnostics when operated as

standard I/O

For using technological functions, please

refer to the

Technological Functions

Manual.

Actuator selection data
Output range (rated values)

Voltage

± 10 V

0 V to 10 V

Current

± 20 mA

0 mA to 20 mA

4 mA to 20 mA

Load resistance (within output rating)

For voltage outputs

Capacitive load

min. 1 kΩ
max. 0.1 μF

For current outputs

Inductive load

max. 300 Ω
0.1 mH

Advertising