background image

Technical data of CPU 31x

7.4 CPU 315-2 DP

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

7-15

Technical data
Number of function modules and communication

processors you can operate

FM

Max. 8

CP (PtP)

Max. 8

CP (LAN)

Max. 10

Time-of-day
Real-time clock

Yes (HW clock)

Buffered

Yes

Buffered period

Typically 6 weeks (at an ambient temperature of

104 °F)

Behavior of the clock on expiration of the

buffered period

The clock keeps running, continuing at the time-

of-day it had when power was switched off.

Accuracy

Deviation per day: < 10 s

Operating hours counter

1

Number

0

Value range

2

31

hours

(if SFC 101 is used)

Granularity

1 hour

Retentive

yes; must be manually restarted after every

restart

Clock synchronization

Yes

In the PLC

Master

On MPI

Master/slave

S7 signaling functions
Number of stations that can log in for signaling

functions (e.g. OS)

16
(depends on the number of connections

configured for PG / OP and S7 basic

communication)

Process diagnostics messages

Yes

Simultaneously enabled interrupt S blocks

40

Testing and commissioning functions
Status/control variables

Yes

Variables

Inputs, outputs, memory bits, DBs, timers,

counters

Number of variables

Of those as status variable

Of those as control variable

30
30
14

Forcing

Variables

Inputs/Outputs

Number of variables

Max. 10

Block status

Yes

Single step

Yes

Breakpoints

2