Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 122

Advertising
background image

Technical data of CPU 31xC

6.3 CPU 313C

CPU 31xC and CPU 31x, Technical data

6-12

Manual, Edition 08/2004, A5E00105475-05

Technical data
can be used for

PG communication

Reserved (default)

Configurable

Max. 7
1
from 1 to 7

OP communication

Reserved (default)

Configurable

Max. 7
1
from 1 to 7

S7 basic communication

Reserved (default)

Configurable

Max. 4
4
from 0 to 4

Routing

No

Interfaces
1st interface
Type of interface

Integrated RS485 interface

Physics

RS 485

electrically isolated

No

Interface power supply

(15 to 30 VDC)

Max. 200 mA

Functionality

MPI

Yes

PROFIBUS DP

No

PtP communication

No

MPI

Services

PG/OP communication

Yes

Routing

No

Global data communication

Yes

S7 basic communication

Yes

S7 communication

As server

As client

Yes

No (but via CP and loadable FBs)

Transmission rates

max. 187.5 kbps

Programming
Programming language

LAD/FBD/STL

Available instructions

see the Instruction List

Nesting levels

8

System functions (SFCs)

see the Instruction List

System function blocks (SFBs)

see the Instruction List

User program security

Yes

Advertising