Cycle and reaction times

5.2 Cycle time

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

5-7

Operating system processing time at the scan cycle checkpoint

The table below shows the operating system processing time at the scan cycle checkpoint of

the CPUs. These times are calculated without taking into consideration times for:

Testing and commissioning routines, e.g. status/controlling of variables or block status

functions

Transfer and deletion of blocks, compressing user program memory

Communication

Read/write access to the MMC, using SFC82 to 84

Table 5-6

Operating system processing time at the scan cycle checkpoint

CPU

Cycle control at the scan cycle check point (CCP)

312C

500 μs

313C

500 μs

313C-2

500 μs

314C-2

500 μs

312

500 μs

314

500 μs

315

500 μs

317

150 μs

Extension of the cycle time as a result of nested interrupts

Enabled interrupts also extend cycle time. Details are found in the table below.

Table 5-7

Extended cycle time due to nested interrupts

Interrupt type Process

interrupt

Diagnostic

Interrupt

Time-of-day

interrupt

Delay interrupt

Watchdog

interrupt

312C

700 μs

700 μs

600 μs

400 μs

250 μs

313C

500 μs

600 μs

400 μs

300 μs

150 μs

313C-2

500 μs

600 μs

400 μs

300 μs

150 μs

314C-2

500 μs

600 μs

400 μs

300 μs

150 μs

312

700 μs

700 μs

600 μs

400 μs

250 μs

314

500 μs

600 μs

400 μs

300 μs

150 μs

315

500 μs

600 μs

400 μs

300 μs

150 μs

317

190 μs

240 μs

200 μs

150 μs

90 μs

The program runtime at interrupt level must be added to this time extension.