Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 40

Advertising
background image

Communication

3.2 Communication services

CPU 31xC and CPU 31x, Technical data

3-12

Manual, Edition 08/2004, A5E00105475-05

Routing network nodes: MPI – DP - Ethernet

CPU 1

(e.g. 315-2 DP)

PN

Subnet 3 (PROFInet)

PN

PG

Subnet 2 (PROFIBUS)

DP

(master)

MPI

Subnet 1 (MPI)

MPI/DP

(active slave)

CPU 2

(317-2 PN/DP)

CPU 3

(317-2 PN/DP)

Number of routed connections

The CPUs with DP interface provide a different number of connections for the routing

function:

Table 3-5

Number of routing connections for DP CPUs

CPU

As of firmware version

Number of connections for routing

31xC, CPU 31x

2.0.0

Max. 4

317-2 DP

2.1.0

Max. 8

31x-2 PN/DP

2.2.0

Interface X1 configured as:

MPI: Max. 10

DP master Max. 24

DP slave (active): Max. 14


Interface X2 configured as:

PROFINET Max. 24

Advertising