3.1 Interfaces

CPU 31xC and CPU 31x, Technical data

3-2

Manual, Edition 08/2004, A5E00105475-05

Devices capable of MPI communication

PG/PC

OP/TP

S7-300 / S7-400 with MPI interface

S7-200 (19.2 kbps only)

3.1.2

PROFIBUS DP

Availability

CPUs with “DP“ name suffix are equipped at least with a DP X2 interface.
The 315-2 PN/DP and 317 CPUs are equipped with an MPI/DP X1 interface. A CPU with

MPI/DP interface is supplied with a default MPI configuration. You need to set DP mode in

STEP 7 if you want to use the DP interface.

Operating modes for CPUs with two DP interfaces

Table 3-1

Operating modes for CPUs with two DP interfaces

MPI/DP interface (X1)

PROFIBUS DP interface (X2)

MPI

DP master

DP slave

1

not configured

DP master

DP slave

1

1

simultaneous operation of the DP slave on both interfaces is excluded

Properties

The PROFIBUS DP interface is mainly used to connect distributed I/O. PROFIBUS DP

allows you to create large subnets, for example.
The PROFIBUS DP interface can be set for operation in master or slave mode, and supports

transmission rates up to 12 Mbps.
The CPU broadcasts its bus parameters (transmission rate, for example) via the

PROFIBUS DP interface when master mode is set. A PG, for example, can thus receive the

correct parameters and automatically connect to a PROFIBUS subnet. In your configuration

you can specify to disable bus parameter broadcasting.