Communication

3.1 Interfaces

CPU 31xC and CPU 31x, Technical data

3-4

Manual, Edition 08/2004, A5E00105475-05

Devices capable of PROFINET (PN) communication

PROFINET IO components (for example, interface module IM 151-3 PN in an ET 200S)

S7-300 / S7-400 with PROFINET interface (for example, CPU 317-2 PN/DP or

CP 343-1 PN)

Active network components (a switch, for example)

PG/PC with network card

Properties of PROFINET interface X2

Properties
IEEE standard

802.3

Connector design

RJ45

Transmission speed

Max. 100 Mbps

Media

Twisted Pair Cat5 (100BASE-TX)

Note
Networking PROFINET components
The use of switches, rather than hubs, for networking PROFINET components brings about

a substantial improvement in decoupling bus traffic, and improves runtime performance

under higher bus load. PROFINET CBA with cyclic PROFINET interconnections requires the

use of switches in order to maintain compliance with performance specifications. Full duplex

mode at 100 Mbps is mandatory for cyclic PROFINET interconnections.
PROFINET IO also requires the use of switches and 100 Mbps full duplex mode.

Reference

For information on how to configure the integrated PROFINET interface of the CPU, refer

to the

S7-300, CPU 31xC and CPU 31x Installation operating manual.

For details on PROFINET, refer to the

PROFINET System Description

For detailed information on Ethernet networks, network configuration and network

components refer to the

SIMATIC NET Manual: Twisted Pair and Fiber Optic Networks,

available under article ID 8763736 on the Internet URL

http://www.siemens.com/automation/service&support

Tutorial: Commissioning Component-Based Automation Systems, article ID 14142554

Further information on PROFINET: http://www.profibus.com