Communication

3.2 Communication services

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

3-25

Establishing a connection for communication

FB 65 "TCON" establishes communication between the CPU and a communication partner.

You can establish up to eight connections. The CPU automatically monitors and holds the

active connection.
Communication partner A must initiate the connection. When the connection of

communication partner A is active, it transmits a request to connect to communication

partner B. Communication partner B waits until it receives the request for a passive

connection.
In your connection configuration, you define which communication partner activates the

connection, and which communication partners respond to the request with a passive

connection.
Both communication partners must have established their connection in order to be able to

exchange data.

Data exchange

Bidirectional data exchange is enabled after you established communication, that is, data

can be transmitted and received in parallel. FBs available for data exchange:

Name of the FB

Description

FB 63 "TSEND"

Transmit data

FB 64 "TRCV"

Receive data

You can transmit and receive up to 1460 bytes of user data.

Disconnecting

FB 66 "TDISCON" disconnects the CPU from a communication partner.

Communication interruptions

Events causing interruptions of communication:

You program the cancellation of connections at FB 66 "TDISCON."

The CPU goes from RUN to STOP.

At POWER OFF / POWER ON

Reference

For detailed information on the blocks described earlier, refer to the

STEP 7 Online Help.