Technical data of CPU 31xC

6.4 CPU 313C-2 PtP and CPU 313C-2 DP

CPU 31xC and CPU 31x, Technical data

6-20

Manual, Edition 08/2004, A5E00105475-05

Technical data

CPU 313C-2 PtP

CPU 313C-2 DP

Integrated functions

Counters

3 channels (see the Manual

Technological Functions

)

Frequency counters

3 channels, max. 30 kHz (see the Manual

Technological Functions

)

Pulse outputs

3 channels for pulse width modulation, max. 2.5 kHz (see the Manual

Technological Functions

)

Controlled positioning

No

Integrated "Controlling" SFB

PID controller (see the Manual

Technological Functions

)

Dimensions

CPU 313C-2 PtP

CPU 313C-2 DP

Mounting dimensions W x H x D (mm)

120 x 125 x 130

Weight

approx. 566 g

Voltages and currents

CPU 313C-2 PtP

CPU 313C-2 DP

Power supply (rated value)

24 VDC

Permitted range

20.4 V to 28.8 V

Current consumption (no-load operation) Typically 100 mA
Inrush current

Typically 11 A

Power consumption (nominal value)

700 mA

900 mA

I

2

t

0.7 A

2

s

External fusing of power supply lines

(recommended)

LS switch type B: min. 4 A, type C: min. 2 A

Power loss

Typically 10 W

Reference

In Chapter

Specifications of the integrated I/O are found

under

Digital inputs of CPUs 31xC and Digital outputs of CPUs 31xC the technical data of

integrated I/Os.

the block diagrams of the integrated I/Os under

Arrangement and usage of integrated

I/Os.