Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 162

Advertising
background image

Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data

6-52

Manual, Edition 08/2004, A5E00105475-05

Technical data
Time constant of the input filter

0,38 ms

Basic processing time

1 ms

Interference suppression, error limits
Interference voltage suppression for f = nx (f1 ± 1 %), (f1 = interference

frequency), n = 1, 2

Common­mode interference (U

CM

< 1.0 V)

> 40 dB

Feedback interference (peak value of the interference < rated value of

the input range)

> 30 dB

Crosstalk between the inputs

> 60 dB

Operational error limits (across the temperature range, in relation to input

range)

Voltage/current

< 1 %

Resistance

< 5 %

Basic error limit (operational limit at 25 °C, in relation to input range)

Voltage/current

< 0,7 %

Resistance

< 3 %

Temperature error (in relation to input range)

± 0,006 %/K

Linearity error (referred to input range)

± 0,06 %

Repeat accuracy (in transient state at 25 °C, in relation to input range)

± 0,06 %

Status, interrupts, diagnostics
Interrupts

no interrupts when operated as standard

I/O

Diagnostics functions

no diagnostics when operated as

standard I/O

For using technological functions, please

refer to the

Technological Functions

Manual.

Encoder selection data
Input ranges (rated value)/input resistance

Voltage

± 10 V/100 kΩ

0 V to 10 V/100 kΩ

Current

± 20 mA/50 Ω

0 mA to 20 mA/50 Ω

4 mA to 20 mA/50 Ω

Resistance

0 Ω to 600 Ω/10 MΩ

Resistance thermometer

Pt 100/10 MΩ

Permitted continuous input voltage (destruction limit)

For voltage inputs

Max. 30 V

For current inputs

Max. 2.5 V

Permitted continuous input current (destruction limit)

For voltage inputs

Max. 0,5 mA;

For current inputs

Max. 50 mA;

Advertising