Cycle and reaction times

5.3 Response time

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

5-17

5.3.3

Longest response time

Conditions for the longest response time

The figure below shows the conditions under which the longest response time is reached.

Response time

While reading in the PII, the status of the monitored
input changes. This change of the input signal is not
included in the PII any longer.

The change of the input signal is included in the PII.

The change of the input signal is processed by the
application program.

The response of the user program to the change
of the input signal is issued to the outputs.

Delay of inputs +

2 x DP cycle time at PROFIBUS DP

Delay of outputs +

2 x DP cycle time at PROFIBUS DP

CCP (OS)

PIO

PII

CCP (OS)

PIO

PII