Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 159

Advertising
background image

Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

6-49

Technical data

Table 6-13 Technical data of digital outputs

Technical data

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Module-specific data

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Number of outputs

6

16

16

16

2

4

4

4

Of those are fast outputs

Caution:
You cannot connect the high-speed outputs of your CPU in parallel.

Cable length

Unshielded

Max. 600 m

Shielded

Max. 1000 m

Voltage, currents, potentials

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Rated load voltage L+

24 VDC

Polarity reversal protection

No

Total current of outputs (per group)



Max. 2.0 A

Max. 3,0 A

Max. 3,0 A

Max. 3,0 A

Horizontal assembly

up to 104 °F

up to 60 °C

Max. 1,5 A

Max. 2.0 A

Max. 2.0 A

Max. 2.0 A

Vertical assembly

up to 104 °F

Max. 1,5 A

Max. 2.0 A

Max. 2.0 A

Max. 2.0 A

Electrical isolation

Between channels and the backplane bus Yes

No

Yes

Yes

Yes

Between the channels

In groups of

8

8

8

Permitted potential difference

Between different circuits

75 VDC / 60 VAC

Insulation test voltage

500 VDC

Current consumption

with load voltage L+

Max. 50 mA

Max. 100 mA

Max. 100 mA

Max. 100 mA

Status, interrupts, diagnostics

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Status display

green LED per channel

Interrupts

no interrupts when operated as standard I/O

For using technological functions, please refer to the

Technological

Functions

Manual.

Diagnostics functions

no diagnostics when operated as standard I/O

For using technological functions, please refer to the

Technological

Functions

Manual.

Advertising