Cycle and reaction times

5.2 Cycle time

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

5-13

Additional marginal conditions

The maximum cycle load through communication in the measurement is 20 %.
The lower graphic shows that the OB1 cycle is influenced by increasing the cyclical

PROFINET interconnections to remote partners at PROFINET:

0

32

64

96

128

160

200

0

2

4

6

8

10

12

14

Cycle time in ms

Dependency of the OB1 cycle on the number of interconnections

Number of interconnections

OB1 cycle with 32 remote
PROFINET partners

OB1 cycle with 5 remote
PROFINET partners

Base load through PROFIBUS devices

The 16 PROFIBUS devices with their interconnections among each other generate an

additional base load of up to 1,0 ms.

Tips and notes

The upper graphic already includes the use of uniform values for the transfer frequency of all

interconnections to a partner.

The performance can drop by up to 50 % if the values are distributed to different

frequency levels.

The use of data structures and arrays in an interconnection instead of many single

interconnections with simple data structures increases the performance.