3 system status lists (ssls) in profinet io – Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 51

Advertising
background image

Communication

3.2 Communication services

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

3-23

3.2.10.3 System status lists (SSLs) in PROFINET IO

Chapter Content

This chapter explains the following:

Which SSLs are intended for PROFINET

Which SSLs are intended for PROFIBUS DP

Which SSLs are intended for both PROFINET IO and PROFIBUS DP

Compatibility of the new SSLs

For PROFINET IO, it was necessary to create some new SSLs, among other things,

because larger configurations are now possible with PROFINET.
You can also use these new SSLs with PROFIBUS.
You can continue to use a known PROFIBUS SSL that is also supported by PROFINET. If

you use an SSL in PROFINET that does not support PROFINET, an error code is returned in

RET_VAL (8083: Index wrong or not permitted).

Comparison of the System Status Lists of PROFINET and PROFIBUS

Table 3-9

Comparison of the System Status Lists of PROFINET and PROFIBUS

SSL-ID

PROFINET IO

PROFIBUS DP

Applicability

W#16#0591

yes

(parameter adr1 changed)

Yes

Module status information for the interfaces of a

module/submodule

W#16#0A91

yes

(parameter adr1 changed)

Yes

Status information of all subsystems and master

systems (S7-300 without CPU 318-2 DP)

W#16#0C91

yes

(parameter adr1/adr2 and

expected/actual type ID

changed)

Yes

Module status information of a module/submodule in a

central configuration or attached to an integrated DP or

PN interface module using the logical address of the

module.

W#16#4C91

yes

(parameter adr1 changed)

Yes

Not with S7-300
Module status information of a module/submodule

attached to an external DP or PN interface module

using the start address

W#16#0D91

yes

(parameter adr1 changed)

Yes

Module status information of all modules in the

specified rack/station

new:

W#16#0696

Yes

Yes

Module status information of all submodules of a

module using the logical address of the module, not

possible for submodule 0

new:

W#16#0C96

Yes

Yes

Module status information of a submodule using the

logical address of this submodule

W#16#xy92

No

(replacement: SSL-ID

W#16#0x94)

Yes

Rack/stations status information

Replace this SSL with the SSL with the ID W#16#xy94

in PROFIBUS DP as well.

new:

W#16#0x94

Yes

Yes

Rack/station status information