Technical specifications of the ps 405 4 a – Siemens Simatic S7-400 User Manual

Page 113

Advertising
background image

Power Supply Modules

3-33

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Technical Specifications of the PS 405 4 A

Dimensions, Weight, and Cable Cross-Sections

Dimensions WxHxD (mm)

Weight

25x290x217

0.76 kg

g

Cable cross-section

g

3 x 1.5 mm

2

(litz wire

with wire end ferrule;
use component

use component
conductor or flexible
sheath cable)

Cable diameter

3 to 9 mm

Input Rating

Input voltage

Rated value

Permitted range

24/48/60 VDC

Static:
19.2 VDC to 72 VDC

Dynamic:
18.5 VDC to 75.5 VDC

Rated input current

2 A/1 A/0.8 A

Overvoltage resistance

In accordance with DIN
VDE 0160, curve B2

Output Rating

Output voltages

Rated values

5.1 VDC /24 VDC

Output currents

Rated values

5 VDC: 4 A

24 VDC: 0.5 A

Max. residual ripple

5 VDC: 50 mV

SS

24 VDC: 200 mV

SS

Max. switching peaks

5 VDC: 150 mV

S

24 VDC: 500 mV

S

Idle conditions

5 VDC: 100 mA Base
load required

24 VDC: Idling-proof
(no base load required)

Other Parameters

Protection class in accordance
with IEC 60536

I, with protective
grounding conductor

Overvoltage category

II

Pollution severity

2

Rated voltage U

e

0 < U

e

50 V

150 V < U

e

300 V

Test Voltage

700 VDC
(secondary <–> PE)

2200 VDC
(primary <–> PE)

Buffering of power failures:

> 20 ms
Complies with the
NAMUR
recommendation NE
21 of August 1998 at a
repeat rate of 1 s

Power consumption (24 VDC)

48 W

Power loss

16 W

Backup current

Max. 100

µ

A at power

off

Backup battery (option)

1 x Lithium AA, 3.6 V /
1.9 Ah

Protective separation
to IEC 61131-2

Yes