Cable Duct and Fan Subassemblies

9-8

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Signaling Concept

The signaling concept of the 24 VDC fan subassembly is identical to the signaling
concept of the 120/230 VAC fan subassembly.

Fuse

Included in this fan subassembly are standard cartridge fuse links,
5 x 20 mm, conforming to DIN

1.0 AT for 24 V

The fuse is already installed on shipping from the factory.

Shielding Clamps

If you do not require the shielding clamps supplied, do not install them in the fan
subassembly.

Technical Specifications

Dimensions, Weights

Dimensions WxHxD (mm)

482.5

Ч

109.5

Ч

235

(

)

Weight

appr. 2000 g

Kabeldurchmesser

3 bis 9 mm

Nominal Sizes

Lifespan of the fans

at

40°

C

at

75°

C

70000 h

25000 h

Max. contact load of relay con-
tacts 1 to 6

Switching voltage

Switching current

24 VDC

200 mA

Voltages, Currents, Potentials

Input voltage

Nominal value

Valid range

DC 24 V

Static 19.2 V up to 30
V

Dynamic: 18.5 up to
30.2 V

Starting current

0.9 A at 24 V

Fuses

1.0 AT

Power consumption

with fan

without fan

12 W

1.4 W

!

Caution

Danger of damage to equipment.

If you insert the monitoring PCB in the wrong position in the fan subassembly, the
fan subassembly may be damaged.

During maintenance of the unit, make sure you do not replace the monitoring PCB
in the wrong position.

Monitoring Function

In the case of a fault (defective fans) the fans are not switched off. Once you have
replaced the defective fan(s), the fault is acknowledged automatically as soon as
the fans have reached the required speed. Any faults that occur are not stored.

When you switch on the fan subassembly, the fans start running. After
approximately 10 s the current status of the fans is indicated via LEDs and relays.