Technical specifications of the – Siemens Simatic S7-400 User Manual

Page 144

Advertising
background image

Digital Modules

4-22

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Technical Specifications of the

SM 421; DI 32 x 24 VDC

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 500 g

Data for Specific Module

Number of inputs

32

Length of cable

Unshielded

Shielded

Max. 600 m

Max. 1000 m

Voltages, Currents, Potentials

Power rated voltage of the
electronics L+

Not required

Number of inputs that can be
triggered simultaneously

32

Isolation

Between channels and
backplane bus

Yes

Between the channels

No

Permitted potential difference

Between the different
circuits

75 VDC / 60 VAC

Insulation tested with

Channels against
backplane bus and load
voltage L+

500 VDC

Current consumption

From the backplane bus

Max. 20 mA

Power dissipation of the
module

Typ. 6 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

None

Diagnostic functions

None

Substitute value can be applied

No

Data for Selecting a Sensor

Input voltage

Rated value

For signal “1”

For signal “0”

24 VDC

13 V to 30 V

-30 V to 5 V

Input current

At signal “1”

7 mA

Input delay

At “0” to “1”

At “1” to “0”

1.2 ms to 4.8 ms

1.2 ms to 4.8 ms

Input characteristic curve

To IEC 61131; type 1

Connection of two-wire BEROs

Possible

Permitted bias current

Max. 1.5 mA

Advertising
This manual is related to the following products: