Digital Modules

4-48

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Setting the Input Delay for Channel Groups

You can only set the input delay for each group of channels. In other words, the
setting for channel 0 applies to inputs 0 to 7 and the setting for channel 8 applies to
inputs 8 to 15.

Note

The parameters that are entered for the remaining channels (1 to 7 and 9 to 15)
must be equal to the value 0 or 8, otherwise those channels will be reported as
being incorrectly parameterized.

Any hardware interrupts that have occurred in the meantime will be reported after
acknowledgement.

Optimum Signal Propagation Delays

You can achieve the fastest signal propagation delay with the following settings:

Both channel groups are parameterized with an input delay of 0.5 ms

The Diagnostics parameter is disabled

The Diagnostic Interrupt parameter is disabled