1 commissioning the sm 432; ao 8 x 13 bit – Siemens Simatic S7-400 User Manual

Page 361

Advertising
background image

Analog Modules

5-145

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

5.25.1

Commissioning the SM 432; AO 8

13 Bit

Parameter

You will find a description of the general procedure for assigning parameters to
analog modules in Section 5.7.

You will find an overview of the programmable parameters and their default values
in Table 5-43, on page 5-42.

Assigning Parameters to Channels

You can configure each output channel of the SM 432; AO 8

13 Bit individually.

You can thus assign different parameters to each output channel.

5.25.2

Output Ranges of the Analog Output Module SM 432;
AO 8

13 Bit

Wiring the Analog Outputs

You can wire the outputs as voltage or current outputs, or disable them. You wire
the outputs by means of the “Type of Output” parameter in STEP 7.

Unused Channels

To ensure that output channels of the SM 432; AO 8

13 Bit remain de-energized,

you must disable the “Type of Output” parameter and leave the terminal open.

Output Ranges

You program the output ranges for voltage and current outputs in STEP 7.

Table 5-78 Output Ranges of the Analog Output Module SM 432; AO8

13 Bit

Selected Type of Output

Output Range

Description

Voltage

1 to 5 V
0 to 10 V

"

10 V

You will find the digital
analog values in Section
5.3.2 in the voltage and

t t

t

Current

0 to 20 mA
4 to 20 mA

"

20 mA

current output ranges

Default Settings

The default settings of the module are “Voltage” for the output type and “

"

10 V”

for the output range. You can use this combination of output type and output range
without parameterizing the SM 432; AO 8

13 Bit in STEP 7.

Advertising
This manual is related to the following products: