Interface Submodules

13-52

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

13.7.11

Analog Value Representation for the Measuring Ranges of the
Analog Outputs

Voltage and Current Output Ranges

Table 13-44 contains the representation of

The voltage output range

±

10 V and

The current output range

±

20 mA.

Table 13-44

Representation of the Analog Output Ranges (Voltage and Current Output Ranges)

Range

Units

Output Range

Output Range

Range

Decimal

Hexadecimal

"

10 V

"

20 mA

Overflow

≥(

32512

≥(

7F00

H

11.851 V

Overrange

32496

:

27664

7EF0

H

:

6C10

H

11.7534 V

:

10.0005 V

Nominal range

27648

:

0

:

-27648

6C00

H

:

0

H

:

9400

H

10 V

:

0 V

:

-10 V

20 mA

:

0 mA

:

-20 mA

Underrange

-27664

:

-32512

93F0

H

:

8100

H

-10.0005 V

:

-11.759 V

Underflow

-32528

≤(

80F0

H

-11.851 V