A5E00069467-07

Technical Specifications of the SM 421; DI 16

x

120/230 VUC

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 650 g

Data for Specific Module

Number of inputs

16

Length of cable

Unshielded

Shielded

600 m

1000 m

Voltages, Currents, Potentials

Power rated voltage of the
electronics L+

None

Number of inputs
that can be triggered
simultaneously

16

Isolation

Between channels and
backplane bus

Yes

Between the channels

Yes

In groups of

4

Permitted potential difference

Between M

internal

and the

inputs

250 VAC

Between the inputs of the
different groups

500 VAC

Insulation resistance

4000 VAC

Current consumption

From the backplane bus

Max. 80 mA

Power dissipation of the
module

Typ. 12 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

None

Diagnostic functions

None

Substitute value can be applied

No

Data for Selecting a Sensor

Input voltage

Rated value

For signal “1”

120/230 VUC

74 to 264 VAC
80 to 264 VDC
–80 to –264 VDC

For signal “0”

0 to 40 VAC
–40 to +40 VDC

Frequency range

47 to 63 Hz

Input current

At signal ”1” (120 V)

Typ. 10 mA AC
Typ. 1.8 mA DC

At signal ”1” (230 V)

Typ. 14 mA AC
Typ. 2 mA DC

At signal “0”

0 to 6 mA AC
0 to 2 mA DC

Input delay

At “0” to “1”

Max. 20 ms AC
Max. 15 ms DC

At “1” to “0”

Max. 30 ms AC
Max. 25 ms DC

Input characteristic curve

To IEC 61131;
type 2

Connection of two-wire BEROs

Permitted bias current

Possible

Max. 5 mA AC