1 module overview, Introduction – Siemens Simatic S7-400 User Manual

Page 125

Advertising
background image

Digital Modules

4-3

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

4.1

Module Overview

Introduction

The following tables summarize the most important characteristics of the digital
modules. This overview is intended to make it easy to choose the suitable module
for your task.

Table 4-1

Digital Input Modules: Characteristics at a Glance

Module

Characteristics

SM 421;

DI 32

24

VDC

(-1BL0x-)

SM 421;

DI 16



24

VDC

(-7BH00-)

SM 421;

DI 16



120

VAC

(-5EH00-)

SM 421;

DI 16



24/

60 VUC

(-7DH00-)

SM 421;

DI 16



120

/230 VUC
(-1FH00-)

SM 421;

DI 16



120

/230 VUC
(-1FH20-)

SM 421;

DI 32



120

VUC

(-1EL00-)

Number of
inputs

32 DI;
isolated in
groups of
32

16 DI;
isolated in
groups of 8

16 DI;
isolated in
groups of 1

16 DI;
isolated in
groups of 1

16 DI;
isolated in
groups of 4

16 DI;
isolated in
groups of 4

32 DI;
isolated in
groups of 8

Rated input
voltage

24 VDC

24 VDC

120 VAC

24 VUC to
60 VUC

120 VAC/
230 VDC

120/230
VUC

120 VAC/
VDC

Suitable for...

Switches

Two-wire proximity switches (BEROs)

Programmable
diagnostics

No

Yes

No

Yes

No

No

No

Diagnostic
Interrupt

No

Yes

No

Yes

No

No

No

Hardware
interrupt upon
edge change

No

Yes

No

Yes

No

No

No

Adjustable input
delays

No

Yes

No

Yes

No

No

No

Substitute value
output

Yes

Special Features

High
packaging
density

Quick and
with
interrupt
capability

Channel-
specific
isolation

Interrupt
capability
with low,
variable
voltages

For high,
variable
voltages

For high,
variable
voltages

Input
characterist
ic curve to
IEC
61131-2

High
packaging
density

Advertising