Diagnostic Data of the Signal Modules

B-17

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Bytes 8 to 23 of the SM 431; AI 8

RTD

16 Bit

Data record 1 with bytes 8 to 23 contains channel-specific diagnostic data. The
following figure shows the assignment of the even diagnostic bytes (bytes 8, 10, to
22) for a channel of the module.

7 6

0

Configuring/parameter assignment error

Wire break

Underflow

Overflow

5 4 3 2 1

0

0

0

0

Figure B-22

Even Diagnostic Byte for a Channel of the SM 431; AI 8 x RTD x 16 Bit

The following figure shows the assignment of the odd diagnostic bytes (bytes 9,
11, to 23) for a channel of the module.

7 6

0

User connection not wired

Run time calibration error

Underrange or overrange

5 4 3 2 1

0

Open conductor in + direction

Open conductor in – direction

Open conductor in the current source

User calibration doesn’t correspond to the parameter assignment

Figure B-23

Odd Diagnostic Byte for a Channel of the SM 431; AI 8 x RTD x 16 Bit