3 technical specifications – Siemens Simatic S7-400 User Manual

Page 556

Advertising
background image

Interface Submodules

13-60

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

13.8.3

Technical Specifications

Technical Specifications

The IF 961-CT1 interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.

6ES7961-3AA00-0AC0

Technical Specifications

Supply voltage

Supplied from the
M7-400
programmable
modules or from the
M7-300/400
expansion modules

Current consumption in the
M7-300
(for dimensioning the 24 V
current supply)

0.053 A

Current consumption in the
M7-400
(for dimensioning the 5 V
current supply)

0.15 A

Nominal voltage load
current supply
2L+ / 2M

24 VDC

Current consumption
2L+ / 2M

Depends on the
load of the digital
outputs

Type ID

03

H

Power losses

1.5 W

Dimensions
W x H x D (mm)

18.2 x 67 x 97

Weight

0.07 kg

Counter Inputs 5 V

Number of counter
channels

1, alternative to 24 V

Level

In accordance to
RS422

Terminating resistance

approx. 220 ohms

Differential voltage

min 0.5 V

Sensor voltage

No

Sensor monitoring

Yes

Counter range

32 bits

Max. counter frequency

500 kHz

Counter Inputs 24 V

Number of counter
channels

1, alternative to 5 V

Low level
High level

- 30 V to + 5 V
+ 11 V to + 30 V

Input resistance

1 k

W

Input current

typ. 7 mA

Sensor voltage

No

Sensor monitoring

No

Counter range

32 bits

Max. counter frequency

200 kHz

Digital Inputs

Supply voltage

2L+ / 2M

Number of inputs

4

Low level
High level

- 30 V to + 5 V
+ 11 V to + 30 V

Input current

typ. 7 mA

Galvanic isolation

Yes, to all others
except the digital
outputs

Input filter
(can be set)

50 kHz, 200 kHz

Digital Outputs

Supply voltage

2L+ / 2M

Number of outputs

2

Galvanic isolation

Yes, to all others
except the digital
inputs

Output voltage
– Low level
– High level

max. 3 V
2 L+ - 1.5 V

Switching current
– Nominal value
– Range

0.3 A
5 mA to 0.3 A

Switching time

max. 300 ms

Cutoff voltage (inductive)

Limited to
2L+ +

(

39 V

Short-circuit protection

Yes, via electronic
fuse