Siemens Simatic S7-400 User Manual

Page 401

Advertising
background image

PROFIBUS DP Master Interface IM 467/IM 467 FO

8-3

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

PROFIBUS DP interface
9-pin subminiature D

LEDs

Mode selector

Figure 8-1

Configuration of the IM 467/467 FO

Communication Services

The IM 467/IM 467 FO offers two communication services:

PROFIBUS DP

The IM 467/IM 467 FO is a PROFIBUS DP master in accordance with EN 50
170. It is configured entirely with STEP 7. It behaves in basically the same way
as the integrated PROFIBUS DP interfaces on the CPU modules (see the
technical specifications of the IM 467/IM 467 FO for the differences).

DP communication does not require any function calls in the STEP 7 user
program.

S7 functions

The S7 functions guarantee optimal and easy communication in a
SIMATIC S7/M7/C7 automation solution. The following S7 functions are enabled
for the IM 467/IM 467 FO:

– Programming device functions via PROFIBUS DP

– Operator control and monitoring functions via PROFIBUS DP

Communication takes place without any additional configuration on the IM 467/
IM 467 FO.

S7 functions can be used on their own or in parallel with the PROFIBUS DP
protocol. If they are used in parallel with DP communication, this affects the
PROFIBUS DP bus cycle time.

Advertising
This manual is related to the following products: