Parameter Sets for Signal Modules

A-7

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

A.3

Parameters of the Digital Output Modules

Parameters

The table below contains all the parameters you can set for digital output modules.
The comparison shows:

Which parameters you can change with STEP 7 and

Which parameters you can change with SFC 55 “WR_PARM”

The parameters set with STEP 7 can also be transferred to the module with SFCs
56 and 57 (refer to the STEP 7 manuals).

Table A-3

Parameters of the Digital Output Modules

Parameter

Data Record

No.

Parameters Can Be Assigned

with ...

... SFC 55

... STEP 7

Destination CPU for Interrupts

0

No

Yes

Diagnostics

0

No

Yes

Diagnostic interrupt enable

Yes

Yes

Reaction to CPU STOP

1

Yes

Yes

Enable substitute value “1”

Yes

Yes

Note

If you want to enable the diagnostic interrupt in the user program in data record 1,
you must enable the diagnosis in data record 0 beforehand using STEP 7.