Analog Modules

5-82

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Status, Interrupts, Diagnostics

Interrupts

None

Diagnostic functions

None

Substitute value can be applied

No

Data for Selecting a Sensor

Input range (rated values)/Input
resistance

Voltage

"

80 mV/1 M

W

"

250 mV/1 M

W

"

500 mV/1 M

W

"

1 V/1 M

W

"

2.5 V/1 M

W

"

5 V/1 M

W

1 to 5 V

/

1 M

W

"

10 V/1 M

W

Current

0 to 20 mA

/

50

W

"

20 mA/50

W

4 to 20 mA

/

50

W

Resistors

0 to 48

W/

1 M

W

0 to 150

W/

1 M

W

0 to 300

W/

1 M

W

0 to 600

W/

1 M

W

0 to 6000

W/

1 M

W

(can be used up to
5000

W

)

Thermocouples

TC type B/1 M

W

TC type R/1 M

W

TC type S/1 M

W

TC type T/1 M

W

TC type E/1 M

W

TC type J/1 M

W

TC type K/1 M

W

TC type U/1 M

W

TC type L/1 M

W

TC type N/1 M

W

Resistance thermometer

Pt 100/1 M

W

Pt 200/1 M

W

Pt 500/1 M

W

Pt 1000/1 M

W

Ni 100/1 M

W

Ni 1000/1 M

W

Maximum input voltage for
voltage input (destruction limit)

Max. 18 V continuous
75 V for 1 ms (cycle
factor 1 : 20)

Maximum input current for
current input (destruction limit)

40 mA continuous

Connection of the sensor

For measuring voltage

Possible

For measuring current

As two-wire transmitter

Possible

As four-wire
transmitter

Possible

For measuring resistance

With two-conductor
terminal

Possible; cable
resistance is also
measured

With three-conductor
terminal

Possible

With four-conductor
terminal

Possible

Load of the two-wire
transmitter

Max. 750

W

Characteristic linearization

Parameters can be
assigned

For thermocouples

Types B, R, S, T, E, J,
K, U, L, N

For
resistance thermometers

Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100,
Ni 1000

Temperature compensation

Yes, programmable

Internal temperature
compensation

No

External temperature
compensation with
compensating box

Possible

External temperature
compensation with Pt 100

Possible

Compensation for
definable reference
junction
temperature

Possible

Unit for temperature
measurement

Degrees Celsius

Advertising