PROFIBUS DP Master Interface IM 467/IM 467 FO

8-13

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

8.4.2

Technical Specifications of the IM 467 FO

6ES7 467-5FJ00-0AB0

Dimensions and Weight

Dimensions
W x H x D (mm)

Weight

25 x 290 x 210

700 g

PROFIBUS DP

Standard

Transmission rate

Transmission
technology

PROFIBUS DP,
EN 50 170

9.6 kbps to 12 Mbps,
parameterizable in steps (3
Mbps and 6 Mbps not
possible)

FOC

Wavelength l = 660 nm 2 x
Duplex socket

Current consumption

Current consumption from
the S7-400 bus (24 VDC)
The IM does not consume
any current at 24 V, and it
only makes this voltage
available at the MPI/DP
interface.

Total current consumption
of the components
connected to the DP
interfaces, with a maximum
of
150 mA

PROFIBUS DP

Conditions of Use

Can be used in

SIMATIC S7-400, max. 4
IM 467 in the central
controller

IM 467 cannot be used with the CP 443-5

Supply voltage

5 VDC via the backplane
bus

Current consumption

From 5 VDC

1.3 A

Addressing range

Max. 4 KB for inputs and 4
KB for outputs

DP master

Yes

DPV 1

No

Enable/disable

No

Number of connectable I/O
devices
(slaves)

96

Number of connections for
S7 functions for the
programming device and
operator control and
monitoring

32 + 1 diagnostic
connection

Data volume per slave

Max. 244 bytes

Consistency

Max. 128 bytes

Configuration software

STEP 7

DP slave

No

Deviations from the DP Interface Integrated

in the CPU

Different SSL IDs for system diagnostics

Possibly extended SFC run times

Additional return codes for SFC 14 and
SFC 15