Siemens Simatic S7-400 User Manual

Page 580

Advertising
background image

Diagnostic Data of the Signal Modules

B-6

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Bytes 2 and 3 of the SM 421; DI 16

24/60 VUC

Byte 2

7 6

0

Operating status 0: RUN

1: STOP

5 4 3 2 1

0

Byte 3

7 6

0

EPROM error

Hardware interrupt lost

5 4 3 2 1

0

0 0 0 0

0 0

0 0 0

0 0

Figure B-5

Bytes 2 and 3 of the Diagnostic Data of the SM 421; DI 16 x 24/60 VUC

Bytes 4 to 8 of the SM 421; DI 16

24/60 VUC

Byte 4

7 6

0

5 4 3 2 1

Byte 5

7

0

Channel type B#16#70: digital input

Number of diagnostics bits that the module
outputs per channel: 8 bits long

Byte 6

7

0

Number of channels of the same
type in one module: 16 channels

Byte 7

7 6

0

Channel error, channel 0

Channel error, channel 1

Channel error, channel 6

Channel error, channel 7

5 4 3 2 1

...

0

Byte 8

7 6

0

Channel error, channel 14

Channel error, channel 15

5 4 3 2 1

...

Channel error, channel 8

Channel error, channel 9

Figure B-6

Bytes 4 to 8 of the Diagnostic Data of the SM 421; DI 16 x 24/60 VUC