Siemens Simatic S7-400 User Manual

Page 194

Advertising
background image

Digital Modules

4-72

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Technical Specifications of the SM 422; DO 32

24 VDC/0.5 A

Programming package

Associated programming
package

As of STEP 7 V 2.0

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 600 g

Data for Specific Module

Number of outputs

32

Length of cable

Unshielded

Shielded

600 m

1000 m

Voltages, Currents, Potentials

Power rated voltage of the
electronics L+

24 VDC

Rated load voltage L+

24 VDC

Aggregate current of
the outputs (per supply group
of 8 outputs)

Up to 40

_

C

Up to 60

_

C

Max. 4 A

Max. 2 A

Isolation

Between channels and
backplane bus

Yes

Between the channels

No

Permitted potential difference

Between the different
circuits

75 VDC / 60 VAC

Insulation tested with

Channels against
backplane bus and load
voltage L+

500 VDC

Load voltage L+ against
backplane bus

500 VDC

Current consumption

From the backplane bus

Power supply and load
voltage L+ (no load)

Max. 200 mA

Max. 30 mA

Power dissipation of the
module

Typ. 4 W

Status, Interrupts, Diagnostics

Status display

Green LED per channel

Interrupts

None

Diagnostic functions

None

Data for Selecting an Actuator

Output voltage

At signal “1”

Min. L+ (-0,3 V)

Output current

At signal “1”

Rated value

Permitted range

0.5 A

5 mA to 0.6 A

At signal “0” (leakage
current)

Max. 0.3 mA

Output delay (for resistive
load)

From “ 0” to “1”

Max. 1 ms

At “1” to “0”

Max. 1 ms

Load resistor range

48

W

to 4 k

W

Lamp load

Max. 5 W

Parallel connection of 2
outputs

For redundant triggering of
a load

Possible (only outputs
of the same group)

To increase performance

Possible (only outputs
of the same group)

Triggering a digital input

Possible

Switch rate

For resistive load

Max. 100 Hz

For inductive load
to IEC 947-5-1, DC 13

Max. 2 Hz at 0.3 A
Max. 0.5 Hz at 0.5 A

For lamp load

Max. 10 Hz

Limit (internal) of the inductive
circuit interruption voltage up
to

Typ. – 27 V

Short-circuit protection of the
output

Threshold on

Electronically cyclic

Typ. 0.7 A to 1.5 A

1)

A supply group always consists of eight adjacent

channels starting with channel 0. Channels 0 to 7, 8 to
15, 16 to 23 and 24 to 32 therefore form one supply
group.

Advertising