Analog Modules

5-102

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Technical Specifications of the SM 431; AI 16 x 13 Bit

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 500 g

Data for Specific Module

Number of inputs

Shielded

16

Max. 200 m

Voltages, Currents, Potentials

Rated load voltage L+

24 VDC (only required
for the supply of 2-wire
transmitters)

Reverse polarity protection

Yes

Power supply of the
transmitters

Supply current

Max. 50 mA

Short-circuit proof

Yes

Constant measured current for
resistance-type sensor

Typ. 1.67 mA

Isolation

Between channels and
backplane bus

Between the channels

Between channels and
load voltage L+

No

No

No

Permitted potential difference

Between inputs and M

ANA

(U

CM

)

Between the inputs (E

CM

)

2 VDC/2 VAC

SS

2 VDC/2 VAC

SS

Insulation tested with

Between bus and chassis
ground

500 VDC

Current consumption

From the backplane bus

Max. 100 mA

From load voltage L+
(with 16 connected, fully
controlled two-wire
transmitters)

Max. 400 mA

Power dissipation of the
module

Typ. 2 W

Analog Value Generation

Measuring principle

Integrative

Integration time/conversion
time/resolution (per channel)

(Does not go into the
response time)

Parameters can be
assigned

Yes

Interference voltage
suppression f1 in Hz

60/50

Integration time in
milliseconds

50/60

Basic conversion time in
ms

55/65

Resolution including sign

13 bits

Smoothing of the measured
values

Not possible

Basic execution time of the
module, in ms (all channels
enabled)

880/1040

Suppression of Interference, Limits of Error

Interference voltage suppression for f = nx (f1

"

1%),

(f1 = interference frequency) n = 1, 2, ...

Common-mode
interference
(U

CM

< 2 V)

> 86 dB

Series-mode interference
(peak value of interference
< rated value of input
range)

> 60 dB

Crosstalk between the inputs

> 50 dB

Operational limit (in the entire temperature range, with
reference to the input range)

Voltage input

"

1 V

"

10 V

1 V to 5 V

"

0.65%

"

0.65%

"

1 %

Current input

"

20 mA

4 mA to 20 mA

"

0.65%

"

0.65%

Basic error (operational limit at 25

°

C, referred to input

range)

Voltage input

"

1 V

"

10 V

1 V to 5 V

"

0.25%

"

0.25%

"

0.5%

Current input

"

20 mA

4 mA to 20 mA

"

0.25%

"

0.25%

Temperature error (with
reference to the input range)

"

0.01%

Linearity error (with reference
to the input range)

"

0.05%

Repeat accuracy (in the steady
state at 25

°

C, referred to the

input range)

"

0.01%

Status, Interrupts, Diagnostics

Interrupts

None

Diagnostic functions

None

Substitute value can be applied

No

Advertising