17 analog module interrupts – Siemens Simatic S7-400 User Manual

Page 283

Advertising
background image

Analog Modules

5-67

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

5.17

Analog Module Interrupts

Introduction

In this Section, the interrupt behavior of the analog modules is described. The
following interrupts exist:

Diagnostic Interrupt

Hardware interrupt

Note that not all analog modules have interrupt capability or they are only capable
of a subset of the interrupts described here Refer to the technical specifications of
the modules, starting at Section 5.18, to find out which analog modules have
interrupt capability.

The OBs and SFCs mentioned below can be found in the online help system for
STEP 7, where they are described in greater detail.

Enabling Interrupts

The interrupts are not preset – in other words, they are inhibited without
appropriate parameter assignment. You enable interrupts in STEP 7
(refer to Section 5.7).

Special Feature: The Module is Inserted in ER-1/ER-2

Note

If you use the analog module in ER-1/ER-2, you must set the parameters for the
input of all the interrupts to “No” because the interrupt lines are not available in
ER-1/ER-2.

Diagnostic Interrupt

If you have enabled diagnostic interrupts, then active error events (initial
occurrence of the error) and departing error events (message after troubleshooting)
are reported by means of an interrupt.

The CPU interrupts the execution of the user program and processes the
diagnostic interrupt block (OB 82).

In the user program, you can call SFC 51 or SFC 59 in OB 82 to obtain more
detailed diagnostic information from the module.

The diagnostic information is consistent until such time as OB 82 is exited. When
OB 82 is exited, the diagnostic interrupt is acknowledged on the module.

Advertising
This manual is related to the following products: