Siemens Simatic S7-400 User Manual

Page 50

Advertising
background image

General Technical Specifications

S7-400, M7-400 Programmable Controllers Module Specifications

1-22

A5E00069467-07

1.6.2

Use of the S7-400 in a Zone 2 Hazardous Area

Zone 2

Hazardous areas are divided up into zones. The zones are distinguished according
to the probability of the existence of an explosive atmosphere.

Zone Explosion

Hazard

Example

2 Explosive

gas

atmosphere

occurs only seldom and for a
short time

Areas around flange joints with flat
gaskets in pipes in enclosed spaces

Safe area

No

Outside zone 2

Standard distributed I/O

applications

Below you will find important information on the installation of the SIMATIC S7-400
in a hazardous area.

Further Information

You will find further information on the various S7-400 modules in the manual.

Production Location

Siemens AG, Bereich A&D
Östliche Rheinbrückenstraße 50
76187 Karlsruhe
Germany

Certification

II 3 G

EEx nA II T3 .. T6

in accordance with EN 50021 : 1999

Test number: KEMA 03ATEX1125 X

Note

Modules with

II 3 G EEx nA II T3 .. T6 certification can only be used in

SIMATIC S7-400 automation systems belonging to equipment category 3.

Advertising
This manual is related to the following products: