15 connecting loads/actuators to current outputs – Siemens Simatic S7-400 User Manual

Page 278

Advertising
background image

Analog Modules

5-62

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

5.15

Connecting Loads/Actuators to Current Outputs

Note

The necessary connecting cables, which result from the potential connection of the
analog output module, are not drawn in the figures shown below.

In other words, you must continue to take note of and implement Section 5.13 with
its generally applicable information for connecting loads/actuators.

Abbreviations and Mnemonics Used in the Figure Below

The abbreviations and mnemonics used in the figure below have the following
meanings:

Q

I

:

Analog output current

M

ANA

:

Reference potential of analog circuit

R

L

:

Load impedance

L +:

Terminal for 24 VDC supply voltage

M :

Ground terminal

U

ISO

:

Potential difference between M

ANA

and chassis ground

Connecting Loads to a Current Output

You must connect loads to Q

I

and the reference point of the analog circuit M

ANA

of

a current output.

+24 V

R

L

L

+

QI

M

ANA

M

0 V

U

ISO

Chassis ground

Figure 5-23

Connecting Loads to a Current Output of an Isolated AO

Advertising
This manual is related to the following products: