Analog Modules

5-106

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Unused Channels

Unused channels can usually be left open. Put the measuring range modules in
position “B”. You can improve the noise immunity of the module in a measuring
environment with serious interference by connecting M– and chassis ground.

Disable the “Measuring Type” parameter for unused channels. In this way you
shorten the scan time of the module.

Measuring Ranges

You set the measuring ranges by means of the measuring range modules on the
module and the “Measuring Type” parameter in STEP 7.

Table 5-63 Measuring Ranges of the SM 431; AI 16 x 13 Bit

Method Selected

Measuring Range

(Type of Sensor)

Measuring Range

Module Setting

Description

U: Voltage

"

1 V

A

You will find the digitized analog

l

i S

ti

5 3 1 i th

1 to 5 V

"

10 V

B

values in Section 5.3.1 in the
voltage measuring range

2DMU: Current
(two-wire transmitter)

4 to 20 mA

D

To supply these transmitters with
current you must connect 24 V to
the L+ and M front connector
terminals.

You will find the digitized analog
values in Section 5.3.1 in the
current measuring range

4DMU: Current
(four-wire transmitter)

4 to 20 mA

"

20 mA

C

You will find the digitized analog
values in Section 5.3.1 in the
current measuring range

Default Settings

The default settings of the module in STEP 7 are “Voltage” for the measuring
method and “

"

10 V” for the measuring range. You can use this combination of

measuring method and measuring range without parameterizing the SM 431;
AI 16

13 Bit inSTEP 7.