Siemens Simatic S7-400 User Manual

Page 126

Advertising
background image

Digital Modules

4-4

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Table 4-2

Digital Output Modules: Characteristics at a Glance

Module

Characte-
ristics

SM 422;

DO 16

24

VDC/2 A

(-1BH1x)

SM 422;

DO

16

20-125

VDC/1.5 A

(-5EH10)

SM 422;

DO

32

24

VDC/ 0.5 A

(-1BL00)

SM 422;

DO 32

24

VDC/0.5 A

(-7BL00)

SM 422;

DO

8

120/230

VAC/5 A
(-1FF00)

SM 422; DO

16

120/230

VAC/2 A

(-1FH00)

SM 422;

DO

16

20-120

VAC/2 A

(-5EH00)

Number of
outputs

16 DO;
isolated in
groups of 8

16 DO;
isolated
and reverse
polarity
protection
in groups of
8

32 DO;
isolated in
groups of
32

32 DO;
isolated in
groups of 8

8 DO;
isolated in
groups of 1

16 DO;
isolated in
groups of 4

16 DO;
isolated in
groups of 1

Output current

2 A

1.5 A

0.5 A

0.5 A

5 A

2 A

2 A

Rated load
voltage

24 VDC

20 to 125
VDC

24 VDC

24 VDC

120/
230 VAC

120/
230 VAC

20 to
120 VAC

Programmable
diagnostics

No

Yes

No

Yes

No

No

Yes

Diagnostic
Interrupt

No

Yes

No

Yes

No

No

Yes

Substitute
value output

No

Yes

No

Yes

No

No

Yes

Special
Features

For high
currents

For variable
voltages

High
packaging
density

Particularly
quick and
with
interrupt
capability

For high
currents
with
channel-
specific
isolation

For variable
currents
with
channel-
specific
isolation

Table 4-3

Relay Output Module: Characteristics at a Glance

Module

Characteristics

SM 422; DO 16

30/230 VUC/Rel. 5 A

(-1HH00)

Number of Outputs

16 outputs, isolated in groups of 8

Load Voltage

125 VDC

230 VAC

Special Features

Advertising
This manual is related to the following products: