5.24.1

Commissioning the SM 431; AI 8

16 Bit

You set the mode of operation of the SM 431; AI 8

16 Bit in STEP 7.

Parameter

You will find a description of the general procedure for assigning parameters to
analog modules in Section 5.7.

An overview of the parameters that you can set and their default settings are
shown in the table below.

Table 5-74 Parameters of the SM 431; AI 8

16 Bit

Parameter

Value Range

Default

2)

Parameter

Type

Scope

Enable

Diagnostic interrupt

1)

Hardware interrupt

1)

Yes/no
Yes/no

No
No

Dynamic

Module

Destination CPU for
interrupt

1 to 4

Static

Module

Trigger for hardware
interrupt

3)

Dynamic

Channel

High limit

Low limit

32767 to – 32768

– 32768 to 32767


Dynamic

Channel

Diagnostics

Wire break

Reference channel
error

Underflow

Overflow

Yes/no
Yes/no

Yes/no
Yes/no

No
No

No
No

Static

Channel

Measurement

Measuring method

Disabled
U

Voltage

4DMU

Current
(four-wire transmitter)

TC-L

Thermocouple (linear)

TC-L

Static

Channel

Measuring range

Refer to Section 5.24.2 for the
measuring ranges of the input
channels that you can set.

Type J

Reference
temperature

– 273.15 to 327.67

o

C

–327.68 to 327.67

o

F

100

o

C

Dynamic

Module

Temperature unit

4)

Degrees Celsius; degrees Fahrenheit

Degrees
Celsius

Interference
suppression

400 Hz; 60 Hz; 50 Hz; 10 Hz

60 Hz

Static