Siemens Simatic S7-400 User Manual

Page 326

Advertising
background image

Analog Modules

5-110

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Technical Specifications of the SM 431; AI 16

16 Bit

Programming package

Associated programming
package

As of STEP 7 V 2.0

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 500 g

Data for Specific Module

Number of inputs

For resistance-type sensor

16

8

Length of cable

Shielded
in the input ranges

x

80

mV and with
thermocouples

Max. 200 m
Max. 50 m

Voltages, Currents, Potentials

Rated load voltage L+

24 VDC (only required
for the supply of
two-wire transmitters)

Reverse polarity protection

Yes

Power supply of the
transmitters

Supply current

Max. 50 mA

Short-circuit proof

Yes

Constant measured current for
resistance-type sensor

Typ. 1.67 mA

Isolation

Between channels and
backplane bus

Between the channels

Between channels and
load voltage L+

Yes

No

Yes

Permitted potential difference

Between inputs and M

ANA

(U

CM

)

120 VAC

Between the inputs (E

CM

)

120 VAC

Between M

ANA

and

M

internal

(U

ISO

)

75 VDC/60 VAC

Insulation tested with

Between bus and L+/M

Between bus and analog
section

Between bus and chassis
ground

Between analog section
and L+/M

Between analog section
and chassis ground

Between L+/M and chassis
ground

2120 VDC

2120 VDC

500 VDC

707 VDC

2120 VDC

2120 VDC

Current consumption

From the backplane bus

Max. 700 mA

From load voltage L+
(with 16 connected, fully
controlled two-wire
transmitters)

Max. 400 mA

Power dissipation of the
module

Typ. 4.5 W

Analog Value Generation

Measuring principle

Integrative

Integration time/conversion
time/resolution (per channel)

(Does not go into the
response time)

Parameters can be
assigned

Yes

Interference voltage
suppression f1 in Hz

400/60/50

Integration time in ms

2.5/16.7/20

Basic conversion time in
ms

6/20.1/23.5

Additional conversion time
for measuring resistance,
in ms

12/40.2/47

Additional conversion time
for open-circuit monitoring,
in ms

4.3/4.3/4.3

Additional conversion time
for measuring resistance
in ms

5.5/5.5/5.5

Resolution including sign

16/16/16 bit

Smoothing of the measured
values

Parameters can be
assigned in 4
stages

Basic execution time of the
module, in ms (all channels
enabled)

96/322/376

Advertising
This manual is related to the following products: