Siemens Simatic S7-400 User Manual

Page 393

Advertising
background image

IM 463-2

7-9

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Setting the Address Area

The address area of the S5 I/O modules is set on the IM 314. This setting applies
only for the digital and analog I/O modules.

The address areas P, Q, IM3, and IM4 are available. Set the switch to the relevant
position to address the digital and analog I/O modules in these areas.

Table 7-5

Settings Address Areas on the IM 314

I/O Area Address

Switch Position

P area:

F000 - F0FF

Q area:

F100 - F1FF

IM3 area: FC00 - FCFF

IM4 area: FD00 - FDFF

O = OFF,

1 = ON

S1:

0000 *)

0001

1100

1101

OFF

ON

not relevant

*) Status as shipped

Advertising
This manual is related to the following products: