Siemens Simatic S7-400 User Manual

Page 341

Advertising
background image

Analog Modules

5-125

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Technical Specifications of the SM 431; AI 8

RTD

16 Bit

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 650 g

Data for Specific Module

Number of inputs

For resistance-type sensor

8

4

Length of cable

Shielded

Max. 200 m

Voltages, Currents, Potentials

Constant current for
resistance-type sensor

Max. 1 mA

Isolation

Between channels and
backplane bus

Yes

Permitted potential difference

Between M

ANA

and

M

internal

(U

ISO

)

120 VAC

Insulation tested with

1500 VAC

Current consumption

From the backplane bus

Max. 650 mA

Power dissipation of the
module

Typ. 3.3 W

Analog Value Generation

Measuring principle

Integrative

Integration/conversion time/
resolution (per channel)

Parameterizable

(Does not go into the
response time)

Yes

Basic conversion time in
ms

22/25

Additional conversion time
for measuring resistance,
in ms

Max. 200

Resolution including sign

16/16 bit

Noise suppression
for interference frequency
f1 in Hz

60/50

Smoothing of the measured
values

Parameters can be
assigned in 4 stages

Basic response time of module
(all channels enabled)

22/25 ms

Suppression of interference, Limits of Error

Noise suppression for f = n

(f1

"

1%),

(f1 = interference frequency) n = 1, 2, etc.

Common-mode
interference (U

CM

< 120V)

Series-mode interference
(peak value of interference
< rated value of the input
range)

> 100 dB

> 50 dB

Crosstalk between the inputs

> 70 dB

Operational limit (over entire temperature range, referred
to 0 to 60

_

C input range)

RTD input

"

1.0

°

C

Basic error (operational limit at 25

°

C, referred to input

range)

RTD input

"

0.5

°

C

Temperature error (with
reference to the input range)

"

0.007%/K

Linearity error (with reference
to the input range)

"

0.2

°

C

Repeat accuracy (in the steady
state at 25

°

C, referred to the

input range)

"

0.2

°

C

Status, Interrupts, Diagnostics

Interrupts

Hardware interrupt when
limit has been exceeded

Parameters can be
assigned

Diagnostic Interrupt

Parameters can be
assigned

Diagnostic functions

Parameters can be
assigned

Group error display

For internal fault

For external fault

Red LED (INTF)

Red LED (EXTF)

Diagnostic information can
be displayed

Possible

Data for Selecting a Sensor

Input range (rated values) input
resistance

Resistance thermometer

Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100,
Ni 1000

Maximum input voltage for
voltage input (destruction
limit)

35 V continuous;
75 V for max. 1 s
(duty factor 1:20)

Connection of the sensor

For measuring resistance

With three-conductor
terminal

Possible

With four-conductor
terminal

Possible

Characteristic linearization

For resistance
thermometer

Pt 100,0,00385 to DIN
IEC 751

Ni 100, 0,00618 to DIN
43760

Unit for temperature
measurement

Degrees Celsius;
degrees Fahrenheit

Advertising
This manual is related to the following products: