Siemens Simatic S7-400 User Manual

Page 547

Advertising
background image

Interface Submodules

13-51

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

13.7.10

Analog Value Representation for the Measuring Ranges of the
Analog Inputs

Voltage and Current Measuring Ranges

Table 13-43 contains the representation of the digitized measured value for

The voltage measuring range

±

10 V and

The current measuring range

±

20 mA.

Table 13-43

Representation of the Digitized Measured Value for the Analog Input Function (Voltage and
Current Measuring Range)

Range

Measured

Units

Measuring Range

Measuring Range

Range

Measured

Value in %

Decimal

Hexadecimal

"

10 V

"

20 mA

Overflow

≤(

118.51

32767

7FFF

H

≤(

11.851 V

≤(

23.7 mA

Overrange

117.589

:

100.004

32511

:

27649

7EFF

H

:

6C01

H

11.7589 V

:

10.0004 V

23.515 mA

:

20.001 mA

Nominal
range

100

:

0

:

-100

27648

:

0

:

-27648

6C00

H

:

0

H

:

9400

H

10 V

:

0 V

:

-10 V

20 mA

:

0 mA

:

-20 mA

Underrange

-100.004

:

-117.59

-27649

:

-32512

93FF

H

:

8100

H

-10.0004 V

:

-11.759 V

-20.001 mA

:

-23.516 mA

Underflow

-118.51

-32768

8000

H

-11.851 V

-23.7 mA

Advertising
This manual is related to the following products: