2 behavior of the sm 422; do 32 x 24 vdc/0.5 a – Siemens Simatic S7-400 User Manual

Page 200

Advertising
background image

Digital Modules

4-78

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

4.20.2

Behavior of the SM 422; DO 32

24 VDC/0.5 A

Effect of Operating Mode and Supply Voltage on the Output Values

The output values of the SM 422; DO 32

24 VDC/0.5 A depend on the

operating mode of the CPU and on the supply voltage of the module.

Table 4-19 Dependence of the Output Values on the Operating Mode of the CPU and on

the Supply Voltage L+ of the SM 422; DO 32

24 VDC/0.5 A

CPU Operating Mode

Power Supply L+
to Digital Module

Output Value of Digital

Module

POWER ON

RUN

L+ exists

CPU value

L+ missing

0 signal

STOP

L+ exists

Substitute value/last value (0
signal preset)

L+ missing

0 signal

POWER
OFF

L+ exists

0 signal

OFF

L+ missing

0 signal

Behavior in the Event of Failure of the Supply Voltage

The failure of the supply voltage of the SM 422; DO 32

24VDC/0.5 A is always

indicated by the EXTF LED on the module. Furthermore, this information is made
available on the module (entry in diagnosis).

Triggering of the diagnostic interrupt depends on the parameter assignment (see
Section 4.20.1).

Advertising
This manual is related to the following products: