Siemens Simatic S7-400 User Manual

Page 39

Advertising
background image

General Technical Specifications

1-11

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Emission of Radio Interference

Interference emission of electromagnetic fields in accordance with EN 55011: Limit
value class A, Group 1.

Table 1-6

Interference emission of electromagnet fields

Frequency Range

Limit Value

From 20 to 230 MHz

30 dB (

m

V/m)Q

From 230 to 1000 MHz

37 dB (

m

V/m)Q

Measured at a distance of 30 m (98.4 ft.)

Emitted interference via the mains AC power supply in accordance with EN 55011:
Limit value class A, group 1.

Table 1-7

Interference emission via the mains AC power supply

Frequency Range

Limit Value

From 0.15 to 0.5 MHz

79 dB (

m

V)Q

66 dB (

m

V)M

From 0.5 to 5 MHz

73 dB (

m

V)Q

60 dB (

m

V)M

From 5 to 30 MHz

73 dB (

m

V)Q

60 dB (

m

V)M

System Perturbation

The products listed in the table below fulfill the requirements of the following
standards for system perturbation:

Harmonic currents:

EN 61000-3-2

Voltage fluctuations and flickering

EN 61000-3-3

Table 1-8

Power Supply Modules that Comply with System Perturbation
Standards

Name

Order Number

PS 407 4 A Power Supply Module

6ES7407-0DA01-0AA0

PS 407 10 A Power Supply Module

6ES7407-0KA01-0AA0

PS 407R 10 A Redundant Power Supply Module

6ES7422-0KR00-0AA0

PS 407 20 A Power Supply Module

6ES7407-0RA01-0AA0