Power Supply Modules

3-4

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

3.2

Redundant Power Supply Modules

Order Numbers and Function

Table 3-2

Redundant power supply modules

Type

Order Number

Input Voltage

Output Voltage

See

Section

PS 407 10A R

6ES7407-0KR00-0AA0

85 VAC to 264 VAC or
88 VDC to 300 VDC

5 VDC/10 A and
24 VDC/1 A

3.8

PS 405 10A R

6ES7405-0KR00-0AA0

19.2 VDC to 72 VDC

5 VDC/10 A and
24 VDC/1 A

3.14

Redundant Operation

If you use two power supply modules of type PS 407 10A R or PS 405 10A R, you
can install a redundant power supply on a mounting rack. We recommend this if
you want to increase the availability of your programmable controller, particularly if
you are operating it on an unreliable power system.

Configuring a Redundant Power Supply

Redundant operation is possible with any of the S7 CPUs and racks described in
this manual. STEP 7 as of V4.02 is also required.

To set up a redundant power supply, insert a power supply module in slots 1 and 3
of the rack. You can then insert as many modules as can be supplied by a single
power supply module. In other words, in redundant operation all the modules can
only draw a total of 10 A.