Compressor models, Figures 66, Front of unit – Liebert Precision Cooling System DS User Manual

Page 101

Advertising
background image

Piping Schematics

91

Figure 66 Primary connection locations—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic

compressor models

Point

Description

X

inches (mm)

Y

inches (mm)

Connection Size / Opening

inches (mm)

R

Refrigerant Access

63 (1600)

13-13/16 (351)

16-7/16 x 4 (418 x 102)

L1

Liquid Line System 1

79-3/16 (2011)

16-3/4 (425)

1/2 Cu Sweat

L2

Liquid Line System 2

76-1/2 (1943)

16-3/4 (425)

1/2 Cu Sweat

G1

Hot Gas Discharge 1

73-7/8 (1876)

16-3/4 (425)

5/8 Cu Sweat

G2

Hot Gas Discharge 2

70-1/8 (1780)

16-3/4 (425)

5/8 Cu Sweat

CD

Condensate Drain*

46 (1168)

29-1/2 (749)

3/4 FPT

W/ Optional Pump

46 (1168)

29-1/2 (749)

1/2 Cu Sweat

HUM

Humidifier Supply Line

53-1/2 (1359)

29 (737)

1/4 Cu Sweat

ECS

Econ-O-Coil Supply

54-7/8 (1394)

22-9/16 (573)

1-5/8 Cu Sweat

ECR

Econ-O-Coil Return

49-3/8 (1254)

30-3/4 (781)

1-5/8 Cu Sweat

HS

Hot Water Reheat Supply

Consult factory

HR

Hot Water Reheat Return

Consult factory

E1

Electrical Connection (High Volt)

55-1/2 (1410)

31-1/4 (794)

2-1/2

E2

Electrical Connection (High Volt)

52-7/16 (1332)

31-1/4 (794)

2-1/2

LV1

Electrical Connection (Low Volt)

2-1/4 (57)

27 (686)

7/8

LV2

Electrical Connection (Low Volt)

2-1/4 (57)

29 (737)

7/8

LV3

Electrical Connection (Low Volt)

2-1/4 (57)

31 (787)

7/8

B

Blower Outlet

21-15/16 (558)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap.

Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.

Blower

Outlet

B

LV1

LV2
LV3

ECS

HUM

ECR

E1 E2

CD

FRONT OF UNIT

86"

(2184 mm)

16-7/16"

(418mm)

L1 L2 G1 G2

R

A

A

Front View

Section A-A

NOTE: Drawing not to scale.

Tolerance on all
piping dimensions
is ±1/2" (13mm)

All dimensions from
rear corner of unit ,
including panels

Y

O

X

35"

(889 mm)

16-1/16"

(408mm)

4" (102mm)

DPN000803
Rev. 2