All compressor models, Through 79 – Liebert Precision Cooling System DS User Manual

Page 114

Advertising
background image

Piping Schematics

104

Figure 79 Primary connection locations—upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all

compressor models

Point

Description

X

inches (mm)

Y

inches (mm)

Connection Size / Opening

inches (mm)

W1

Water/Glycol/GLYCOOL Access (Bottom)

102-15/16 (2615)

9 (229)

3-1/2 x 8 (89 x 203)

W2

Water/Glycol/GLYCOOL Access (Top)

102-15/16 (2615)

9 (229)

3-1/2 x 8 (89 x 203)

W3

Water/Glycol/GLYCOOL Access (Side)

-

-

6 x 17-3/16 (152 x 437)

WS

Water/Glycol/GLYCOOL Supply

-

-

2-1/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

-

-

2-1/8 Cu Sweat

CGD*

Condensate Gravity Drain

-

-

3/4 FPT

CPD

Condensate Pump Discharge (Option)

79-5/16 (2015)

11-7/8 (302)

1/2 Cu Sweat

HUM

Humidifier Supply Line

79-5/16 (2015)

9-7/8 (251)

1/4 Cu Sweat

ECS**

Econ-O-Coil Supply

78-5/8 (1998)

7-7/8 (200)

2-1/8 Cu Sweat

ECR**

Econ-O-Coil Return

78-5/8 (1998)

4-5/8 (117)

2-1/8 Cu Sweat

E1

Electrical Connection (High Voltage)

75-3/8 (1915)

30 (762)

2-1/2

E2

Electrical Connection (High Voltage)

69-7/8 (1775)

30 (762)

2-1/2

LV1

Electrical Connection (Low Voltage)

19-1/2 (495)

29-1/16 (738)

7/8

LV2

Electrical Connection (Low Voltage)

19-1/2 (495)

30-1/2 (775)

7/8

LV3

Electrical Connection (Low Voltage)

19-1/2 (495)

31-15/16 (811)

7/8

* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
** Supplied on Dual-Cool systems only (4-pipe system)

DPN001214
Rev. 1

Front

W3

WS

WR
CGD

CGD*

Top View

Left Side Section View

Front Section View

(Left Front Panel Not Shown)

8"

(203mm)

6"

(152mm)

3-7/8"

(98mm)

17-3/16"

(437mm)

Blower

Outlet

Blower

Outlet

35"

(889mm)

2-7/8"

(73mm)

3-1/2"

(89mm)

LV1
LV2
LV3

14-1/4"

(362mm)

15-7/8"

(403mm)

All dimensions from
rear corner of unit
including panels

NOTE
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is

±

1/2" (13mm).

3. Field-routed alternatives for water/glycol
connections.
4. See submittal page DPN001191 for
blower outlet and deck dimensional data.

4

4

3

3

3

3

3

3