Compressor models, Front of unit – Liebert Precision Cooling System DS User Manual

Page 102

Advertising
background image

Piping Schematics

92

Figure 67 Primary connection locations—downflow, air-Cooled, 28-42kW (8-12 ton) with scroll

compressor models

Point

Description

X

inches (mm)

Y

inches (mm)

Connection Size / Opening

inches (mm)

R

Refrigerant Access

59-5/16 (1507)

14-3/4 (375)

11-3/16 x 4 (284 x 102)

L1

Liquid Line System 1

69-15/16 (1776)

16-13/16 (411)

1/2 Cu Sweat

L2

Liquid Line System 2

67-5/8 (1718)

16-13/16 (411)

1/2 Cu Sweat

G1

Hot Gas Discharge 1

65-1/2 (1664)

16-13/16 (411)

5/8 Cu Sweat

G2

Hot Gas Discharge 2

62-7/16 (1586)

16-13/16 (411)

5/8 Cu Sweat

CD

Condensate Drain*

46 (1168)

29-1/2 (749)

3/4 FPT

W/ Optional Pump

46 (1168)

29-1/2 (749)

1/2 Cu Sweat

HUM

Humidifier Supply Line

53-1/2 (1359)

29 (737)

1/4 Cu Sweat

ECS

Econ-O-Coil Supply

54-7/8 (1394)

22-9/16 (573)

1-5/8 Cu Sweat

ECR

Econ-O-Coil Return

49-3/8 (1254)

30-3/4 (781)

1-5/8 Cu Sweat

HS

Hot Water Reheat Supply

Consult factory

HR

Hot Water Reheat Return

Consult factory

E1

Electrical Connection (High Volt)

55-1/2 (1410)

31-1/4 (794)

2-1/2

E2

Electrical Connection (High Volt)

52-7/16 (1332)

31-1/4 (794)

2-1/2

LV1

Electrical Connection (Low Volt)

2-1/4 (57)

27 (686)

7/8

LV2

Electrical Connection (Low Volt)

2-1/4 (57)

29 (737)

7/8

LV3

Electrical Connection (Low Volt)

2-1/4 (57)

31 (787)

7/8

B

Blower Outlet

21-15/16 (557)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do

not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.

4" (102 mm)

11-3/16"

(284mm)

ECS

HUM

CD

ECR

E1 E2

R

Blower

Outlet

Section A-A

Front View

16-1/16"

(408mm)

B

A

A

LV3

LV2

LV1

X

Y

O

35"

(889 mm)

All dimensions
from rear corner
of unit including
panels

Tolerance on all
piping dimensions
is ± 1/2" (13mm)

73"

(1854mm)

Front of Unit

Note: Drawing not to scale

DPN000804
Rev. 2

L1 L2 G1 G2